Bathroom Extract Fans from China: The Number on the Box Is Not the Number in Your Bathroom
I had a small order of bathroom fans go wrong last spring and it was not the motor. The customer fitted forty units in a new-build block, and by autumn three of them had mould blooming around the ceiling rose above the shower. The fans ran, you could hear them. They just were not moving the air the spec sheet promised.
The supplier was not lying exactly. They quoted 100 m³/h, which the unit can indeed do if you bolt it to a short duct and let it blow straight into a wall vent. Once it sits behind 2.5 metres of flexible duct with two bends and an external louvre, that same fan is delivering maybe 55 to 60 m³/h. That is the whole story of bathroom extraction in one paragraph.
The box number is free air flow, and free air flow is a lab figure
Free air flow is measured with no resistance at the outlet. It is useful for comparing two models of the same size and almost useless for predicting what happens in a real bathroom. What you want is the flow at the static pressure your installation actually creates, and you want to see that curve, not a single dot.
Ask for a fan curve covering at least 0 to 100 Pa. A typical inline or axial unit that claims 100 m³/h free air will drop to roughly 70 to 75 percent of that at 30 Pa, and to half or less by 60 Pa. A flexible duct is usually the biggest offender, around 3 to 5 Pa per metre depending on how straight it is, and every 90-degree bend adds meaningfully on top. Specced at free air, a bathroom ends up with half the ventilation the drawing promised.
For a normal domestic bathroom the rough working figure is 6 to 10 air changes per hour. Multiply room volume in cubic metres by that, then add a margin for the duct run instead of pretending it is not there. If the calculation gives 60 m³/h at the grille, write 90 to 100 m³/h free air on the purchase order and expect the supplier to argue. That argument is fine. Sending the smaller fan is not.
Static pressure, then noise, and the two are locked together
Any fan pushed toward higher pressure gets louder, so the dB(A) figure on the box is measured at a specific operating point and often at one metre in a free field. Three things quietly inflate it in service. Backdraught shutters rattling in the airstream, flexible duct that has been crushed into a bend because the installer had 300 mm of space, and a wall grille sized too small for the duct. I have seen a 32 dB fan read closer to 45 dB after that last one.
If the plan needs 90 m³/h and the fan is listed at 25 dB, check the curve. It is almost certainly a large unit working well below its maximum. Small high-pressure fans are the ones that whine, and in a bathroom that hums twenty minutes after every shower people stop using the switch.
IP rating for zone 1, and the shutter that leaks in reverse
A fan inside the bathroom near the shower or bath needs IPX4 as a minimum, and the declaration has to cover the actual product, not the family. Ask for the test report and check the model designation in the header against the marking on the unit. It is remarkably common for the report to cover an older housing mould.
Then the backdraft shutter. This is a plastic flap or flap set inside the spigot or at the wall outlet, and its job is to stop cold outside air and smells coming back when the fan is off. A flap that is too stiff sticks open, one too light chatters, and one on a foam seal that has gone hard leaks. In a cold climate a leaking shutter becomes a condensation source, which is how you get black mould on the ceiling around the vent even when the fan works.
Two things to test on the pre-shipment sample: hold a piece of tissue against the grille with the fan off, from inside, and see whether it lifts. Then run the fan and check the flap fully opens rather than flapping at an angle. If it only half opens, the duct is too restrictive and the air is bouncing.
Small things that turn into claims
Timers and humidity sensors are where cheap designs lose the plot. A humidity-triggered fan that switches on at 60 percent relative humidity will run all summer in a humid city, and one set at 85 percent will never trigger. Ask for the set point and whether it is adjustable, and get it written down. The run-on timer after switch-off should be 5 to 15 minutes minimum; 30 seconds is decorative.
Also confirm the mounting. Ceiling fans over a shower get splashed, so the terminal box cover and the cable entry grommet matter. And check that the fan is supplied with the cable clamp, because a unit that arrives without one gets fitted without one.
Finally, small bathroom fans are often sold in the same housing across 100 mm duct, 125 mm duct and 150 mm duct versions, and a supplier will happily swap the spigot size on a running order. Confirm duct diameter per line item on the order, and confirm it again on the box label. A 125 mm fan on a 100 mm hole ends up with tape and hope.
What to put on the order
- Required flow at the grille, plus the duct run described, and a fan curve requested alongside the quote
- IP rating with the test report and the exact model covered
- dB(A) at the stated operating point, not free field only
- Backdraft shutter construction and a tissue test on the sample
- Timer and humidity set points written as numbers on the PO
- Duct diameter per SKU, cable clamp included, terminal cover sealed
None of this is exotic. It is just the difference between buying a fan and buying ventilation, and the first order where you get it wrong is the one that shows up as mould on a ceiling six months later.